Solar panel specs printed on the back of every module tell you how much voltage and current it makes and how those numbers shift with heat and cold, and NEC sections 690.7 and 690.8 use them to set safe string voltage and wire sizes. Read them correctly and your charge controller or inverter stays within its limits for decades. Here’s every line on a typical spec sheet, with worked cold- and hot-weather math.
Electrical work can be dangerous: follow the manual, fuse and size every cable correctly, and use a licensed electrician for anything connected to household wiring.
The Key Solar Panel Specs
| Spec | Meaning | Used for |
|---|---|---|
| Pmax (W) | Rated power at STC | System size |
| Voc | Open-circuit voltage, no load | Max string voltage |
| Vmp | Voltage at max power | MPPT operating window |
| Isc | Short-circuit current | Fuse and wire sizing |
| Imp | Current at max power | Expected operating current |
| Temp. coefficient of Pmax | % power change per °C | Hot-weather output |
| Temp. coefficient of Voc | % or mV per °C | Cold-weather max voltage |
STC (Standard Test Conditions) is 1,000 W/m² sunlight at 25°C cell temperature. Real panels rarely see it, which is why NOCT or NMOT ratings show more realistic output.
Voc and Cold Weather
Panel voltage rises as temperature drops. A typical crystalline panel’s Voc coefficient is around -0.25% to -0.3% per °C. At -10°C (35°C below STC), a 0.28%/°C panel’s Voc rises about 10%.
Example: a 45V Voc panel at -10°C: 45 × (1 + 0.0028 × 35) ≈ 49.4V. Three in series ≈ 148V. That’s within a 150V controller, but with almost no margin. NEC 690.7 sets the method for calculating maximum system voltage.
Vmp and the MPPT Window
An MPPT controller needs the array’s Vmp to be above battery voltage by a margin (often about 5V) to start charging. In hot weather Vmp drops, so check the hot-day value too.
Isc and Fusing
Isc is the most current a panel can produce. NEC 690.8 generally sizes PV circuit conductors and fuses at Isc × 1.25 × 1.25 (1.56 × Isc) for continuous duty and irradiance above STC.
Temperature Coefficient of Power
A Pmax coefficient of -0.35%/°C means a panel at 65°C cell temperature (common on a hot roof) loses about 14% versus STC. Lower numbers are better in hot climates.
How to Read a Solar Panel Spec Sheet
Illustrative label for a 400W residential panel:
| Label line | Example value | What it tells you |
|---|---|---|
| Maximum power (Pmax) | 400W | Output at STC |
| Power tolerance | 0/+5W | It tests at or above 400W |
| Open-circuit voltage (Voc) | 37.0V | Highest voltage, no load |
| Maximum power voltage (Vmp) | 31.0V | Operating voltage at Pmax |
| Short-circuit current (Isc) | 13.6A | Highest current |
| Maximum power current (Imp) | 12.9A | Operating current at Pmax |
| Module efficiency | 20.5% | Watts per square meter of panel |
| Temp. coefficient of Pmax | −0.35%/°C | Power lost per degree above 25°C |
| Temp. coefficient of Voc | −0.27%/°C | Voltage gained per degree below 25°C |
| Maximum system voltage | 1,000V or 1,500V DC | Highest string voltage the module is rated for |
| Maximum series fuse rating | 25A | Largest fuse allowed in series with it |
| NMOT power | about 300W | Output at more realistic conditions |
Check the math: Vmp × Imp = 31.0 × 12.9 ≈ 400W.
STC vs NMOT
| STC | NMOT (or NOCT) | |
|---|---|---|
| Sunlight | 1,000 W/ | 800 W/ |
| Temperature | 25°C cell | 20°C air, with the cell running hotter |
| Wind | n/ | 1 m/ |
| Use | Comparing panels | Estimating real output |
NREL’s PVWatts calculator uses a default system loss of about 14% on top of temperature and sunlight effects, which is one reason real output sits below nameplate.
Cold-Weather Voc: Two Methods
NEC 690.7 lets you calculate maximum voltage using the manufacturer’s temperature coefficient, or a correction table in the code when that isn’t available.
Illustrative: the 37.0V Voc panel above, three in series, at a record low of −20°C (45°C below STC).
| Method | Math | String Voc |
|---|---|---|
| Manufacturer coefficient (−0.27%/°C) | 37.0 × (1 + 0.0027 × 45) × 3 | about 124.5V |
| NEC Table 690.7(A) factor for −16 to −20°C (1.18) | 37.0 × 1.18 × 3 | about 131.0V |
Both stay under a 150V controller, with more margin than the 45V example above. Use the lowest expected temperature for your site, often taken from ASHRAE design data, and the manufacturer’s method when it’s available.
Hot-Weather Vmp: Will the Controller Start?
Illustrative: the same panel at a 65°C cell temperature (40°C above STC), assuming a Vmp coefficient of about −0.35%/°C.
| Math | Result | |
|---|---|---|
| Vmp per panel when hot | 31.0 × (1 − 0.0035 × 40) | about 26.7V |
| Two in series | 26.7 × 2 | about 53V |
| Battery voltage, 48V-class LiFePO4 | about 51–56V | Too close to charge reliably |
| Three in series | 26.7 × 3 | about 80V, a comfortable margin |
Many MPPT controllers need array voltage several volts above battery voltage. Victron’s manuals, for example, say the PV voltage must exceed battery voltage by 5V to start. See MPPT vs PWM.
Isc and NEC 690.8, Worked Out
Illustrative: two strings of the panel above in parallel, Isc 13.6A each.
| Step | Math | Result |
|---|---|---|
| Max circuit current per string (690.8(A)) | 13.6 × 1.25 | 17A |
| Conductor and OCPD sizing (690.8(B)) | 17 × 1.25 | 21.25A |
| Combined output circuit | 2 × 17 | 34A max current |
With only two strings in parallel, string fuses usually aren’t needed, because one string can’t backfeed more than the panel’s maximum series fuse rating. With three or more, the backfeed from the others can exceed it, which is when string fusing comes in. Follow the module and controller manuals. See what size fuse do I need.
Hot-Roof Power Loss
Illustrative, using the −0.35%/°C coefficient:
| Cell temperature | Above STC | Power vs rated |
|---|---|---|
| 25°C | 0°C | 100% |
| 45°C | 20°C | 93% |
| 55°C | 30°C | 89.5% |
| 65°C | 40°C | 86% |
A lower (closer to zero) coefficient helps most in hot climates. Ground mounts with airflow often run cooler than flush roof mounts. See roof mount vs ground mount solar.
Bifacial Panels
Bifacial panels collect light reflected onto the back as well. Spec sheets often list a bifaciality factor, such as 70%, plus extra output at several levels of rear-side gain. The front-side STC rating is still the baseline, and the extra depends on mounting height and the surface underneath, such as white gravel versus grass.
Mechanical Specs on the Datasheet
| Spec | Typical example (illustrative) | Why it matters |
|---|---|---|
| Dimensions | about 1.7 × 1.1 m for a 108-half-cell module | Roof layout and racking |
| Weight | about 21 kg | Handling and roof load |
| Frame | Anodized aluminum, 30–35 mm | Clamp compatibility |
| Connectors | MC4 or MC4-compatible | Mate only with the same type |
| Mechanical load | Front and rear ratings in pascals (Pa) | Snow and wind areas |
| Cable length | about 1.1–1.4 m | Portrait vs landscape stringing |
Mechanical load ratings depend on the clamping zones described in the installation manual, so follow its mounting diagram.
Warranty Specs
Most residential panels list two warranties:
- Product warranty: covers materials and workmanship, often 12–25 years.
- Performance warranty: guarantees a minimum output over time, often around 25–30 years, with a first-year limit and a yearly decline rate.
Illustrative: a performance warranty of 98% in year one and 0.5% a year after that guarantees at least 98 − (0.5 × 24) = 86% of rated power in year 25. See solar panel degradation per year.
FAQ
What solar panel specs matter most?
Voc (cold-weather), Vmp (MPPT window), Isc (fuses and wire) and the power temperature coefficient.
Why does my panel make less than its rated watts?
Heat, angle, dirt and less than STC sunlight. 70-85% of nameplate is common at midday.
Can I mix panels with different specs?
In series, match current (Imp). In parallel, match voltage (Vmp).
What do the specs on a solar panel mean?
Pmax is rated power, Voc and Vmp are voltages, Isc and Imp are currents, and the coefficients show temperature effects.
What is a good temperature coefficient?
Closer to zero is better. Many modern panels list about −0.30 to −0.40%/°C for power.
Where do I find a panel’s spec sheet?
On the label on the back, and as a PDF datasheet on the manufacturer’s website.
Sources: NREL PVWatts documentation; NREL Solar program; NFPA 70 (NEC) 2023 Articles 690.7 and 690.8; NREL PVWatts calculator; Victron Energy SmartSolar MPPT manual. Accessed Oct 2026.
Related: BougeRV Arch Pro 200W Flexible Solar Panel Review, Klein CL390 Clamp Meter Solar Panel Test